S&C Electric Company

Custom Metal-Enclosed Switchgear

Contruction Features — Enclosure

  • Wide bulkhead-type doors provide easy access to all bays
  • Protective screen doors bolt closed. They’re a second barrier, guarding against inadvertent entry to bays containing medium-voltage components
  • Deep 90-degree flanges on the extra-rugged doors assure rigidity and discourage tampering. Sheared edges are folded back, toward the inside of the door, to limit exposure and to help prevent corrosion
  • Three concealed, high-strength latches seal doors shut
  • 11-gauge steel roof, side, and rear sheets; front; and door
  • Full-length doors have three concealed, extra-heavy-duty hinges. Stainless-steel pins won’t corrode, so doors pivot with ease
  • Full side sheets for each bay create double-wall construction between bays
  • Wide-view windows are impact and mar resistant. Let you check switch positions, blown fuse indicators, and status of controls without opening the doors
  • Padlockable window covers — included on Category A enclosures
  • Nameplate provides switchgear ratings
  • Exterior hazard-alerting signs warn the unqualified
  • Flush-mounted key-operated snap locks, plus interlocks and padlocks, help control access to medium-voltage components
  • Padlockable handles on doors and covers shield padlock shackle and thwart tampering. Enclosures specified with Category A construction utilize S&C’s Penta-Lock, providing coordinated latching and padlocking on door handles
  • Integral steel base on all four sides of each bay keeps enclosure rigidly positioned, helps block inter-bay openings at the bottom
  • Interior hazard-alerting signs are unmistakably bold and clear
  • Self-latching door holders securely hold doors open against accidental or windblown closing, unlatch with a touch of the toe for closing
  • Low-voltage wiring is in grounded cable trays, isolated from medium voltage
  • Storage racks keep replacement fuse components in a convenient location
  • Specialized gaskets on outdoor switchgear guard against water entry
  • Insulating “no-drip” compound on inner underside of roof checks condensation
  • Rainproof vent construction keeps water out but lets air circulate to control moisture. Baffles and screens inside the enclosures cover vents, discouraging wire-poking
  • Space heaters for outdoor switchgear maintain air circulation inside enclosure; help keep interior dry
  • S&C’s Ultradur® Finishing System protects steel with multistage pretreatment process of high-pressure-sprayed cleaning, rinsing, phosphatizing, and sealing; durable, baked-on, epoxy powder initial finish coat; and tough, stable, high-solids acrylic topcoat