50/60-Hz ANSI Ratings — IEC Ratings in Parenthesis
kV Amperes, RMS
System Class Max BIL Main Bus
Cont.
Current
Short-
Circuit,
Sym.
Fault Interrupter Load-Interrupter Switch
Cont.
and
Load
Dropping
Ten-Time
Duty-Cycle
Fault-
Interr., Sym.
Cont.
and
Load
Dropping
Mom.
and One-
Second,
Sym.
15.5
(12)
15.5
(15.5)
95
(95)
600
(630)
12 500
(12 500)
200
(200)
12 500
(12 500)
600
(630)
12 500
(12 500)
25 000
(25 000)
600
(630)
25 000
(25 000)
600
(630)
25 000
(25 000)
27
(24)
29
(29)
125
(125)
600
(630)
12 500
(12 500)
200
(200)
12 500
(12 500)
600
(630)
12 500
(12 500)
25 000
(25 000)
600
(630)
25 000
(25 000)
600
(630)
25 000
(25 000)
38
(36)
38
(38)
150
(150)
600
(630)
12 500
(12 500)
200
(200)
12 500
(12 500)
600
(630)
12 500
(12 500)
25 000
(25 000)
600
(630)
25 000
(25 000)
600
(630)
25 000
(25 000)

 Other ratings are available. Contact your local S&C Sales Office for more information.